Language: DE | FR | ES | RU | CN
Datenlogger von Lufft


Measurement Principles and Sensors for Humidity Measurement




Concepts

Relative Humidity

Unit: %

By relative humidity we refer to the ratio of water vapour actually present in the air to the maximum possible mass of water vapour in the air. Relative humidity is usually expressed as a percentage.

The formula applies:

Note: Since maximum humidity is dependent on temperature, relative humidity changes with temperature, even when absolute humidity remains constant.

 

Absolute Humidity

Unit: g/m3

By absolute humidity fabs we refer to the volume of water vapour actually present in a specific quantity of air. Absolute humidity is the ratio of the weight of the water contained in the air and the volume of this moist air.

Water Vapour Partial Pressure, Saturation Vapour Pressure

Unit: hPa

By saturation vapour pressure eS(t) we refer to the maximum possible pressure of the water vapour at a certain temperature. The saturation vapour pressure of water dependent on temperature is presented in the chart below. The water vapour partial pressure e(t) varies between 0 (dry air) and 30hPa. The saturation vapour pressure determines the upper limit.




Saturation humidity, maximum humidity, saturation quantity

Unit: g/m3

By maximum humidity fmax we refer to the maximum possible water vapour quantity in one cubic meter of air at a certain temperature. The moisture absorption capacity of air increases with increasing temperature. If maximum humidity is exceeded, the excess water vapour condenses in the form of condensate (droplet formation).

Dewpoint

Unit: °C, °F, K

By dewpoint temperature ttp we refer to the temperature at which the cooling of moist air leads to condensate formulation. This means that when moist air is cooled down to dewpoint the relative humidity rises to 100%.

Frost Point

Unit: °C, °F, K

In some cases where dewpoint temperatures are below 0°C we refer to the frost point temperature. Other descriptions are also dewpoint temperature above ice or freezing point.

Specific Enthalpy (heat content)

Unit: kJ/kg

By specific enthalpy Espez we refer to the quantity of heat necessary to raise the temperature of a gas (or gas mixture) from one temperature to another at constant pressure.

Or:

By specific enthalpy we refer to the quantity of heat that is available in the air mass relative to a certain air condition. The enthalpy of unsaturated air is the sum of the enthalpy to vaporise the water content present, plus the enthalpy to heat the water vapour mixture to the corresponding temperature.

Mixing Ratio

Unit: g/kg

By mixing ratio m we refer to the ratio of water vapour mass to the mass of dry air.

Wet Bulb Temperature

Unit: °C, °F, K

By wet bulb temperature tF in psychrometric measurement we refer to the temperature output or indicated by a thermometer wrapped in a moist sock. Due to the latent heat of evaporation, this temperature dependent on the relative humidity lies below the air temperature.

Sensors and Measurement Principles

Mechanical Humidity Measurement

The mechanical procedure is based on the expansion and contraction of various (mostly organic) measuring elements. Such measuring elements are, for example: hair, durometers, gut strings, etc. The measuring elements mostly used are hair elements or the so-called Durotherm, an artificial, humidity-sensitive measuring element. The change in length of the measuring element is transferred to the indicator by means of a mechanism.

Hair hygrometers require regular service and maintenance. To avoid drying-out and the associated drift, hair hygrometers must be regularly regenerated. To do this, the hair harp is wrapped in a cloth moistened with distilled water, or sprayed with distilled water, such that saturation occurs. After approximately one hour a measurement value of ca. 98%RH is obtained. A single point adjustment can be carried out on most units using an adjustment screw.

Psychrometric Humidity Measurement

Psychrometers function with two identical, very accurate thermometers, along which the air to be measured is led at a defined speed or over which the air circulates.

The first thermometer measures the ambient air, the second the so-called wet bulb temperature. For this purpose the measurement head of the thermometer is covered by a cotton wick and moistened with distilled water. Both thermometers are placed in an airflow or in moving air and are protected from radiant heat. Due to the latent heat of evaporation the temperature of the wet thermometer falls, and indeed the drier the air, the more so. After a short time (1 - 2 min) the temperature of the wet thermometer remains constant and the measurement values of the wet and dry thermometers can be read. With these two temperatures the relative humidity can be determined in accordance with the following formula :

where A is the so-called psychrometer constant. This depends on the air velocity and is presented in the table below.

Ventilation Speed

0,0

1,0

1,5

2,3

3,4

4,4

A: 106 in Degrees-1

1140

675

674

678

682

704

 
Electronic Humidity Measurement

Capacitive Procedure

The humidity-sensitive condenser consists of two flat electrodes, between which is located an electrically isolating, hygroscopic synthetic coating (dielectric). This dielectric can absorb the water present in the air. With increasing air humidity the capacity of the humidity-sensitive condenser also increases.

The following applies: ,
where e r is the dielectrical constant of the humidity-sensitive condenser.


Dewpoint Mirror Hygrometer

The dewpoint mirror is a very precise measurement procedure for reading relative humidity, wherein the condensation of water vapour is evaluated as it falls below dewpoint. The temperature of a reflected surface (mirror) is cooled down to the point where it begins to be covered in condensation. The temperature measured at this moment by a Pt100 resistance thermometer corresponds to the dewpoint temperature, from which the relative humidity may be calculated by means of the saturation pressure with the aid of the measured air temperature. A Peltier element is installed for cooling, and the mirrored surface is evaluated using an optoelectronic procedure (see drawing).



In contrast to psychrometers the moisture content of the atmosphere is virtually unchanged by the measurement. Dewpoint mirror instruments may therefore also be installed in closed systems such as environmental cabinets.

The mirrors must be cleaned regularly with a suitable liquid, such as trichloroethylene for example.

Comparison of the different procedures

Procedure

Advantages

Disadvantages

     

Mechanical humidity measurement

  • Simple operation
  • Inexpensive
  • Long response times
  • High maintenance cost due to regular regeneration, changing of chart, etc.
  • Limited measuring range
  • Drift

Psychrometric humidity measurement

  • High measurement accuracy
  • High long time stability
  • High reliability
  • Assurance of constant sock wetness
  • Reading errors

Capacitive procedure

  • High measurement accuracy
  • Simple operation
  • Maintenance-free
  • Short response times
  • Good price: performance ratio
  • Temperature compensation of sensor necessary

Dewpoint mirror hygrometer

  • Very high measurement accuracy
  • High reliability
  • High long-term stability
  • Short response times
  • Expensive
  • Maintenance cost due to regular cleaning of mirror
Other humidity measurement procedures

The following is a list of other humidity measurement procedures (detailed observations are not made here):

  • Resistive procedure (determination of the impedance of the alternating current resistance of an hygroscopic element)
  • Lithium chloride dewpoint hygrometer (a measurement procedure based on the hygroscopic characteristic of lithium chloride)