General
Dimensions, probe Length 200mm, Ø 6mm
Dimensions, housing 117x38mm
Weight Approx. 200g
Protection type Housing: plastic (ABS) IP40
Sensor head: stainless steel
Operating temperature 0...50°C
Operating humidity range 0...95% RH
Storage temperature -20...60°C
Storage humidity 20...80% RH
Response time t90 ? 1,5 Sec.
Temperature
Principle Thin-film sensor
Measuring range -20 ... 70 °C
Unit °C
Accuracy ±0.7°C within the range of 0...50°C
Resolution 0.1 °C
Flow
Principle Hot film anemometer
Measuring range 0.08 ... 2 m/s
Unit m/s
Accuracy ± (0.04m/s + 1% of measured value)
Resolution 0.01 m/s